Paper
29 November 2021 Research on leakage protection method based on double terminal residual current sudden changes
Chaoqun Zhou, Shubo Liu, Rongke Sun, Wuyang Ge, Xiankai Chen, Zhihua Zhang
Author Affiliations +
Proceedings Volume 12080, 4th International Symposium on Power Electronics and Control Engineering (ISPECE 2021); 120804E (2021) https://doi.org/10.1117/12.2620241
Event: 4th International Symposium on Power Electronics and Control Engineering (ISPECE 2021), 2021, Nanchang, China
Abstract
In order to overcome the shortcomings of the existing single terminal leakage protection methods, the leakage protection technology based on multi-terminal information should be studied. Based on the analysis of the characteristics of singlephase leakage faults in low-voltage distribution lines, a leakage protection method based on double terminal residual current sudden changes is proposed in this paper, which uses the amplitudes of the double-terminal residual current sudden changes of the protected section as the protection criteria. The protection will act when the double terminal criteria both meet the requirements of their respective setting thresholds. The realization processes and performances of the method are given in the paper. The double terminal residual current information of the protected section is comprehensively utilized by this method, which can effectively eliminate the influence of unbalanced leakage current of line during normal operation and other factors, reduce protection maloperation and improve the utilization rate of protection. It doesn't need multi-level protection delay coordination and has fast action speed; and it has low setting thresholds and high sensitivity. The effectiveness of the method is verified by MATLAB simulation.
© (2021) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Chaoqun Zhou, Shubo Liu, Rongke Sun, Wuyang Ge, Xiankai Chen, and Zhihua Zhang "Research on leakage protection method based on double terminal residual current sudden changes", Proc. SPIE 12080, 4th International Symposium on Power Electronics and Control Engineering (ISPECE 2021), 120804E (29 November 2021); https://doi.org/10.1117/12.2620241
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Resistance

Reliability

Capacitance

Inductance

MATLAB

Power supplies

Signal processing