Paper
11 May 2012 Sound detection monitoring in the transformer oil using fiber optic sensor
Author Affiliations +
Abstract
In this paper it is shown that a fundamental technology of hybrid system combining Sagnac interferometer and FBG. Fiber optic sensor array, i.e. two sensors in the Sagnac loop was suggested. Fiber optic sensor array was fabricated in the transformer oil and external sound applied to the sensor directly using by piezoelectric. Tunable laser source was used as a light source. Applied sound frequency range is from 5kHz to 90kHz. From this experiment it is confirmed that fiber optic sensor using Sagnac interferometer in the transformer oil can detect applied sound frequency. In real electric transformer system suggested fiber optic sensor array can be applied to monitoring physical quantities such as internal temperature, sound pressure and vibration due to partial discharge.
© (2012) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Jongkil Lee "Sound detection monitoring in the transformer oil using fiber optic sensor", Proc. SPIE 8370, Fiber Optic Sensors and Applications IX, 83700W (11 May 2012); https://doi.org/10.1117/12.919441
Lens.org Logo
CITATIONS
Cited by 2 scholarly publications.
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Fiber optics sensors

Sensors

Transformers

Sagnac interferometers

Signal detection

Optical arrays

Acoustics